***problem below is fixed. ***

Dear customer,

Due to a config error Node017 went down for 10 minutes at 17:10
We are busy fixing it.

Log:
17:10 Config error made. Imeediately fixing config error. Network didn't start
17:15 Reboot server. Network still down. Removing files that may cause error. Reboot again
17:20 Server up again.
17:35 Server went down again
17:40 Server up again. At the moment we are looking in the logs what happened this time

Message from Data center what caused the second outage:
Date of issue:                 23 June 2016 Report reference:   -
Incident:    Electric fault at 17.42 and 17.44  23/06/2016 
Failure date/time:   23/06/2016 at 17.42 น.
Restore date/time:   23/06/2016 at 18.50 น.
Failure duration:    1 Hours 8 Minute Failure by:    The electricity system of  MEA.   
Service Impact:  Server and Switch down.  
Root cause:   The electricity system of MEA at transmission line Si Phraya failure, so the circuit breaker of rack is tripped out.   
Solutions:  We will move the electric system non-UPS to UPS.